Test certificates for electricians

Pro Pro is active in this browser. Open your Pro accountPro free trial is active. Open your Pro accountPro is active but will not renew. Open your Pro account

Max Zs Calculator

Choose the device, enter your measured Zs and see whether it is inside the limit.

Example: Max Zs Calculator with the default input (Device type (MCB or RCBO curve): Type B, Rating: 32 A, Also show 80% of the maximum (guidance practice)). The live tool loads here.

Maximum Zs, B32

1.37Ω

80% guidance limit
1.09 Ω
Formula
Zs max = Cmin × U0 / Ia = 0.95 × 230 V / (5 × 32 A) = 1.3656 Ω

Free · runs in your browser · nothing is uploaded

Open on WiringCert

This embed was switched off for this website. Open on WiringCert

Add this tool to your siteFree embed code, no sign-up. Keep the credit link.

Embed this tool

Copy this code into your website, blog or class page. The tool runs inside your page.

Optional settings, added to the address after embed=1: &accent=0f6b5c (colour, 3 or 6 hex digits). Other parameters are ignored.

Please keep the credit link below the tool.

The max Zs calculator works out the highest earth loop impedance (Zs) a circuit can have, and tells you whether a reading you took falls within it. Choose the device type and rating, optionally enter your measured Zs, and the page shows the maximum and the result. It suits anyone checking a circuit, whether you are testing a new installation or reviewing an existing one. It covers circuit breakers of types B, C and D, with ratings from 6 to 125 A, using the BS 7671 formula. Fuses and other devices are not included, so their maximum Zs has to come from the manufacturer’s data.
Max zs example

How to use the Max Zs Calculator

  1. Choose the device type: B, C or D.
  2. Select the rating, from 6 to 125 A.
  3. Optionally, type in the Zs you measured, in ohms.
  4. Read the maximum Zs shown on the page.
  5. Check the result. It will say the reading is within the maximum, within the maximum but above the guidance limit, or over the maximum.
  6. If you want to see or hide the guidance limit, use the guidance tick box.

The link in the address bar keeps the device type, the rating and your reading, so you can open the same result again or send it to a colleague. To keep a value for a circuit on a certificate, you can type it into the certificate editor, which is the route for fuses and other devices whose maximum Zs you have from the manufacturer.

Change the device or the rating and the result updates at once; the guidance tick box changes only the middle outcome. The maximum depends on both the type and the rating, so double-check the label on the breaker before you read the result. Where the circuit is protected by an RCBO, choose its curve type (B, C or D) in the same way as for an MCB.

How is the maximum Zs worked out?

The maximum Zs is the highest earth loop impedance a circuit can have and still disconnect in time under an earth fault. The calculator divides 0.95 x 230 V by k x rating, and k depends on the device type. The formula follows BS 7671 (Regulations 411.4.4 and 411.3.2, and Appendix 3).

Maximum Zs = 0.95 x 230 V / (k x rating)

Device typek
B5
C10
D20

A higher k gives a lower maximum, which matches devices that need a larger fault current to trip quickly.

For example, a type B 32 A device gives 0.95 x 230 / (5 x 32) = 1.37 ohms. 80% of that is 1.09 ohms. A reading of 1.2 ohms is within the maximum but above the guidance limit. A reading of 1.5 ohms is over the maximum, which means the circuit may not disconnect in time.

Which devices does it cover?

MCBs and RCBOs to the BS EN 60898 and BS EN 61009 trip curves, types B, C and D, with ratings from 6 to 125 A. The maximum depends on the instantaneous trip current, so a type D device of a given rating has a much lower maximum than a type B of the same rating. Fuses are left out because their limit comes from a time-current curve that only the manufacturer’s data gives.

What does the 80% guidance limit mean?

The guidance limit is 80% of the maximum Zs. A reading below the maximum but above this limit is allowed, yet it leaves little margin, so it is worth a second look. The limit is a field practice, not a regulation, and the guidance tick box can be switched off if you do not want it.

Every result is a prompt for the certifying electrician, who makes the final decision on the circuit. A reading near the limit should be checked again, and the result is never a pass or fail verdict on its own.

What do typical values look like?

A few worked values for type B devices, from 0.95 x 230 V / (5 x rating): 6 A gives 7.28 ohms, 10 A gives 4.37 ohms, 16 A gives 2.73 ohms and 32 A gives 1.37 ohms. A type C 32 A device gives 0.68 ohm and a type D 32 A device 0.34 ohm. The full list for every rating is on the Maximum Zs Values page.

How this tool works and where the numbers come from

Maximum Zs is calculated as Cmin x U0 / Ia from BS 7671 Regulation 411.4.4 and Appendix 3.

Sources

Reviewed · Published by WiringCert

Frequently asked questions

Why compare a measured Zs with the maximum?

The measured Zs shows the circuit as it actually is, and the maximum is the highest value at which the protective device still disconnects an earth fault in time. The calculator gives you the maximum to compare your reading against.

What if my reading is within the maximum but above the guidance limit?

The reading is still within the maximum, so it is not over it. The tool flags it because it is close to the edge. Check the circuit and retest if you are unsure, and let the certifying electrician decide what to record.

What does it mean if my reading is over the maximum?

A reading over the maximum Zs means the circuit may not disconnect in time under an earth fault. Treat it as a fault to investigate, not a number to round off. Check the connections and the circuit before deciding on the next step.

Can I use the calculator for fuses?

No. Fuses and other devices are not in the calculator. Their maximum Zs comes from the manufacturer’s data, and the certificate editor lets you type that value for a circuit.

Can I switch off the guidance limit?

Yes. The 80% guidance factor is a tick box, so you can turn it off if you only want to check against the maximum. It is a field practice, not a regulation.

How do I share a result?

Copy the link from the address bar. It keeps the device type, the rating and your reading, so the person you send it to sees the same result.