Maximum Zs Values for MCBs and RCBOs

Free, no sign-up, nothing uploaded: pick the device type and see the maximum Zs for every standard rating, worked out from BS 7671:2018+A4:2026 (checked 2026-11-13).

Example: Maximum Zs Values for MCBs and RCBOs with the default input (Device type (MCB or RCBO curve): Type B, Also show 80% of the maximum (guidance practice)). The live tool loads here.

Maximum Zs, type B MCB or RCBO

RatingMaximum ZsGuidance limit
6 A7.28 Ω5.83 Ω
10 A4.37 Ω3.50 Ω
16 A2.73 Ω2.19 Ω
20 A2.19 Ω1.75 Ω
25 A1.75 Ω1.40 Ω
32 A1.37 Ω1.09 Ω
40 A1.09 Ω0.87 Ω
50 A0.87 Ω0.70 Ω
63 A0.69 Ω0.55 Ω
80 A0.55 Ω0.44 Ω
100 A0.44 Ω0.35 Ω
125 A0.35 Ω0.28 Ω

Rule review pending: this rule has not yet been checked against the printed BS 7671:2018+A4:2026 text.

Free · runs in your browser · nothing is uploaded

Open on WiringCert

This embed was switched off for this website. Open on WiringCert

Add this tool to your siteFree embed code, no sign-up. Keep the credit link.

Embed this tool

Copy this code into your website, blog or class page. The tool runs inside your page.

Optional settings, added to the address after embed=1: &accent=0f6b5c (colour, 3 or 6 hex digits). Other parameters are ignored.

Please keep the credit link below the tool.

The Maximum Zs Values table shows the maximum earth fault loop impedance (max Zs), in ohms, for every standard rating from 6 A to 125 A. Pick breaker type B, C or D and the limit for each rating appears in the table. Each figure is worked out from BS 7671 using the instantaneous trip current, so the limit holds for both the 0.4 s and the 5 s disconnection times. The table applies to MCBs and RCBOs to BS EN 60898 and BS EN 61009 on a single-phase 230 V TN system. Use it as a quick reference when you are testing a circuit and want a max Zs figure to compare your measured Zs against. Every value is a prompt for the certifying electrician, not a decision.
Maximum zs values example

How to use the Maximum Zs Values Table

The table needs only two choices from you: the breaker type and the breaker rating. Once both are set, the maximum Zs for that device is on screen.

  1. Choose the breaker type: B, C or D. Select the type printed on your device, because the same rating gives a different limit for each type.
  2. Find the row for your device rating. The ratings listed are 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 and 125 A.
  3. Read the maximum Zs in ohms from the column for that rating.
  4. If you want the guidance figure, tick the box for the 80% column. Its values appear next to the main column.
  5. Untick the same box to switch the 80% column off again.
  6. Take your measured Zs to the Max Zs Calculator to compare it with the limit you have just read.

The 80% column is optional. Leave it off when you only need the standard figures from BS 7671, and turn it on only when you want the guidance values alongside them.

The table changes as soon as you pick a type. For a device that is not an MCB or RCBO, such as a fuse, the table has no row; use the manufacturer’s data and type the value into the certificate editor. The link in the address bar keeps the type and the state of the guidance box, so you can send the same table to a colleague.

How is maximum Zs calculated?

The maximum Zs value is the highest earth fault loop impedance, in ohms, that a circuit can have while its protective device still disconnects a fault in the required time. It is calculated as Cmin × U0 ÷ Ia, where Cmin is 0.95, U0 is 230 V, and Ia is the instantaneous trip current of the device. The limit is a ceiling: a measured Zs above it means the device may not disconnect in time.

The table takes Ia as 5 × In for type B, 10 × In for type C and 20 × In for type D, where In is the device rating. These multipliers follow BS 7671 Regulations 411.4.4 and 411.3.2 and Appendix 3. Because the maximum uses the instantaneous trip current, the same figure holds for the 0.4 s and the 5 s disconnection times.

TypeRatingMax Zs (Ω)
B6 A7.28
B10 A4.37
B16 A2.73
B32 A1.37
C6 A3.64
C16 A1.37
C32 A0.68
D6 A1.82
D16 A0.68
D32 A0.34

These are selected values. The table lists every standard rating for each type.

Each result carries a “rule review pending” mark until it has been checked against the printed BS 7671:2018+A4:2026 text, so confirm the figure against the printed regulations before you rely on it.

What is the acceptable maximum Zs value for a 20 A type B breaker?

Work it out with the same formula used for every rating: Cmin of 0.95 multiplied by U0 of 230 V, divided by the instantaneous trip current. For a type B device, that trip current is 5 times the 20 A rating. The table gives the finished result once you select type B and the 20 A row, so you do not need to calculate it by hand.

Worked example: for a 20 A type B device, Ia is 5 × 20 = 100 A, and 0.95 × 230 = 218.5, so the maximum Zs is 218.5 ÷ 100 = 2.185 Ω, shown in the table as 2.19 Ω (rounded to two decimals).

If you want to check the figure yourself, follow these steps:

  1. Work out Ia for type B: 5 × 20 A.
  2. Multiply Cmin by U0: 0.95 × 230 V.
  3. Divide the result of step 2 by the Ia from step 1.
  4. Compare your answer with the type B, 20 A entry in the table. The two should match.

How this tool works and where the numbers come from

Maximum Zs is calculated as Cmin x U0 / Ia from BS 7671 Regulation 411.4.4 and Appendix 3, with Ia the device’s instantaneous trip current.

Sources

Reviewed · Published by WiringCert

Frequently asked questions

Where to find the maximum Zs in BS 7671?

The limits come from the calculation in Regulations 411.4.4 and 411.3.2, with the trip current multipliers set out in Appendix 3. Check the printed BS 7671:2018+A4:2026 text for the exact wording before you use a figure on site.

Why do the maximum earth fault loop impedance values differ between publications?

The figure depends on its inputs: the Cmin factor, the supply voltage U0, and the trip current multiplier for each device type. The table uses Cmin of 0.95, U0 of 230 V and the multipliers above, so a publication that uses different inputs or a different edition of the regulations can give a different figure. Check which version each source is based on.

Does the 80% column change the limit?

No. The 80% column is a field rule of thumb, not a regulation. The maximum assumes the conductors are at operating temperature, and a Zs measured when the circuit is cold will be lower, so the 80% figure gives you a margin for that. You can switch the column off with the tick box.

Does it cover fuses?

No. Fuses and other devices need the manufacturer’s data; in the certificate editor you type that maximum Zs in for the circuit.