Maximum Zs Values for MCBs and RCBOs
Free, no sign-up, nothing uploaded: pick the device type and see the maximum Zs for every standard rating, worked out from BS 7671:2018+A4:2026 (checked 2026-11-13).
Maximum Zs, type B MCB or RCBO
| Rating | Maximum Zs | Guidance limit |
|---|---|---|
| 6 A | 7.28 Ω | 5.83 Ω |
| 10 A | 4.37 Ω | 3.50 Ω |
| 16 A | 2.73 Ω | 2.19 Ω |
| 20 A | 2.19 Ω | 1.75 Ω |
| 25 A | 1.75 Ω | 1.40 Ω |
| 32 A | 1.37 Ω | 1.09 Ω |
| 40 A | 1.09 Ω | 0.87 Ω |
| 50 A | 0.87 Ω | 0.70 Ω |
| 63 A | 0.69 Ω | 0.55 Ω |
| 80 A | 0.55 Ω | 0.44 Ω |
| 100 A | 0.44 Ω | 0.35 Ω |
| 125 A | 0.35 Ω | 0.28 Ω |
Rule review pending: this rule has not yet been checked against the printed BS 7671:2018+A4:2026 text.
Free · runs in your browser · nothing is uploaded

How to use the Maximum Zs Values Table
The table needs only two choices from you: the breaker type and the breaker rating. Once both are set, the maximum Zs for that device is on screen.
- Choose the breaker type: B, C or D. Select the type printed on your device, because the same rating gives a different limit for each type.
- Find the row for your device rating. The ratings listed are 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 and 125 A.
- Read the maximum Zs in ohms from the column for that rating.
- If you want the guidance figure, tick the box for the 80% column. Its values appear next to the main column.
- Untick the same box to switch the 80% column off again.
- Take your measured Zs to the Max Zs Calculator to compare it with the limit you have just read.
The 80% column is optional. Leave it off when you only need the standard figures from BS 7671, and turn it on only when you want the guidance values alongside them.
The table changes as soon as you pick a type. For a device that is not an MCB or RCBO, such as a fuse, the table has no row; use the manufacturer’s data and type the value into the certificate editor. The link in the address bar keeps the type and the state of the guidance box, so you can send the same table to a colleague.
How is maximum Zs calculated?
The maximum Zs value is the highest earth fault loop impedance, in ohms, that a circuit can have while its protective device still disconnects a fault in the required time. It is calculated as Cmin × U0 ÷ Ia, where Cmin is 0.95, U0 is 230 V, and Ia is the instantaneous trip current of the device. The limit is a ceiling: a measured Zs above it means the device may not disconnect in time.
The table takes Ia as 5 × In for type B, 10 × In for type C and 20 × In for type D, where In is the device rating. These multipliers follow BS 7671 Regulations 411.4.4 and 411.3.2 and Appendix 3. Because the maximum uses the instantaneous trip current, the same figure holds for the 0.4 s and the 5 s disconnection times.
| Type | Rating | Max Zs (Ω) |
|---|---|---|
| B | 6 A | 7.28 |
| B | 10 A | 4.37 |
| B | 16 A | 2.73 |
| B | 32 A | 1.37 |
| C | 6 A | 3.64 |
| C | 16 A | 1.37 |
| C | 32 A | 0.68 |
| D | 6 A | 1.82 |
| D | 16 A | 0.68 |
| D | 32 A | 0.34 |
These are selected values. The table lists every standard rating for each type.
Each result carries a “rule review pending” mark until it has been checked against the printed BS 7671:2018+A4:2026 text, so confirm the figure against the printed regulations before you rely on it.
What is the acceptable maximum Zs value for a 20 A type B breaker?
Work it out with the same formula used for every rating: Cmin of 0.95 multiplied by U0 of 230 V, divided by the instantaneous trip current. For a type B device, that trip current is 5 times the 20 A rating. The table gives the finished result once you select type B and the 20 A row, so you do not need to calculate it by hand.
Worked example: for a 20 A type B device, Ia is 5 × 20 = 100 A, and 0.95 × 230 = 218.5, so the maximum Zs is 218.5 ÷ 100 = 2.185 Ω, shown in the table as 2.19 Ω (rounded to two decimals).
If you want to check the figure yourself, follow these steps:
- Work out Ia for type B: 5 × 20 A.
- Multiply Cmin by U0: 0.95 × 230 V.
- Divide the result of step 2 by the Ia from step 1.
- Compare your answer with the type B, 20 A entry in the table. The two should match.
How this tool works and where the numbers come from
Maximum Zs is calculated as Cmin x U0 / Ia from BS 7671 Regulation 411.4.4 and Appendix 3, with Ia the device’s instantaneous trip current.
Sources
- BS 7671:2018+A4:2026 Requirements for Electrical Installations (IET Wiring Regulations): publisher page, bibliographic reference; not checked against the printed text (BS 7671:2018+A4:2026) · checked
- IEC 61009-1 (BS EN 61009-1): RCBOs, bibliographic reference for RCD trip times and tripping curves (Edition 4.0, published 2024-11-21) · checked
Frequently asked questions
Where to find the maximum Zs in BS 7671?
The limits come from the calculation in Regulations 411.4.4 and 411.3.2, with the trip current multipliers set out in Appendix 3. Check the printed BS 7671:2018+A4:2026 text for the exact wording before you use a figure on site.
Why do the maximum earth fault loop impedance values differ between publications?
The figure depends on its inputs: the Cmin factor, the supply voltage U0, and the trip current multiplier for each device type. The table uses Cmin of 0.95, U0 of 230 V and the multipliers above, so a publication that uses different inputs or a different edition of the regulations can give a different figure. Check which version each source is based on.
Does the 80% column change the limit?
No. The 80% column is a field rule of thumb, not a regulation. The maximum assumes the conductors are at operating temperature, and a Zs measured when the circuit is cold will be lower, so the 80% figure gives you a margin for that. You can switch the column off with the tick box.
Does it cover fuses?
No. Fuses and other devices need the manufacturer’s data; in the certificate editor you type that maximum Zs in for the circuit.
Related tools
- EICR Certificate Maker: use it when you need to build a full EICR report from your test results.
- EICR Codes: C1, C2, C3 and FI: use it when you need to decide which observation code applies to a finding.
- Max Zs Calculator: use it when you have a measured Zs and need to compare it with the limit.
- Earth Fault Loop Impedance Calculator: use it when your question is about earth fault loop impedance itself rather than the limit.
- Ring Final Circuit Test Calculator: use it when you are testing a ring final circuit.
- Insulation Resistance Test: Test Voltage and Minimum: use it when you need the test voltage and the minimum insulation resistance.
- RCD Test: Trip Time Checker: use it when you are checking RCD trip times.
- Earth Electrode Resistance (Ra) Checker: use it when you are checking an earth electrode.
- Prospective Fault Current Calculator: use it when you need the fault current at a point in the installation.