Test certificates for electricians

Pro Pro is active in this browser. Open your Pro accountPro free trial is active. Open your Pro accountPro is active but will not renew. Open your Pro account

Prospective Fault Current Calculator

Enter an impedance or the tester reading and see whether the device can break the current.

Example: Prospective Fault Current Calculator with the default input (Nominal voltage to earth, Uo (V): 230). The live tool loads here.

Enter the impedance, or the tester's reading in kA.

Free · runs in your browser · nothing is uploaded

Open on WiringCert

This embed was switched off for this website. Open on WiringCert

Add this tool to your siteFree embed code, no sign-up. Keep the credit link.

Embed this tool

Copy this code into your website, blog or class page. The tool runs inside your page.

Optional settings, added to the address after embed=1: &accent=0f6b5c (colour, 3 or 6 hex digits). Other parameters are ignored.

Please keep the credit link below the tool.

This prospective fault current calculator works out the current that could flow in a circuit during a fault. It is also known as pfc or prospective short circuit current. Enter the nominal voltage to earth, Uo, and a loop impedance in ohms, or enter the prospective fault current your tester shows in kA. The page returns the result in kA and in amperes, then lets you choose a rated breaking capacity from the preferred miniature circuit-breaker values and tells you whether the current is within it. Use it when you need to check whether a protective device can safely interrupt the largest fault current at its point in the installation.
Prospective fault current example

How to use the prospective fault current calculator

  1. Check the Uo field first. It is set to 230 V by default, which is the voltage to earth. Change it if your nominal voltage to earth is different.
  2. Enter a loop impedance in ohms. If your tester shows a prospective fault current in kA instead, enter that value in the kA field rather than a loop impedance.
  3. Read the result. The page returns the prospective fault current in kA and in amperes, so you can use whichever unit your paperwork uses.
  4. Choose the rated breaking capacity from the list: 1.5, 3, 4.5, 6, 10, 15, 20 or 25 kA. Pick the value marked on the device in front of you. The list is there for convenience, so check your device before you rely on it.
  5. Read the message that says whether the prospective fault current is within the breaking capacity you chose. If it is not, the device is not rated for the current at that point.

If you have both an impedance and a tester reading, the reading wins and the impedance is ignored. Check that you entered kA, not amperes, in the kA field: 0.66 means 660 amperes. The link in the address bar keeps your entries so that you can come back to the same calculation.

What is prospective fault current?

Prospective fault current, often shortened to pfc, is the largest current that could flow at a point in a circuit if a fault short-circuited it. Prospective short circuit current (PSCC) is the same idea for a short circuit between line and neutral.

For a breaking-capacity check, use the worst case: the larger of the line-neutral and line-earth values, which is usually found at the origin of the installation. Enter the impedance or the tester reading for that one. The current is the voltage divided by the loop impedance, so a low loop impedance gives a high prospective fault current. Every result is a prompt for the certifying electrician, not a decision.

How do I calculate the prospective fault current?

Divide the nominal voltage to earth, Uo, by the loop impedance in ohms, and the answer is the prospective fault current in amperes. The tool does this sum for you and also shows the result in kA. Uo is the voltage between line and earth, so on a three-phase system you use the line-to-earth value too.

  1. Find Uo. The tool uses 230 V by default.
  2. Find the loop impedance in ohms from your loop test at the point you are checking.
  3. Use the impedance behind the larger of the line-neutral and line-earth currents, because that is the worst case.
  4. Divide Uo by the loop impedance to get the current in amperes.
  5. Read the kA figure the tool shows and compare it with the breaking capacity of your device.

Worked example: 230 V divided by 0.35 ohm is 657 A, which is 0.66 kA.

What values should I expect?

The sum is only Uo divided by the impedance, so the current rises as the impedance falls. At 230 V, these impedances give:

Loop impedanceProspective fault current
1.00 ohm230 A (0.23 kA)
0.50 ohm460 A (0.46 kA)
0.35 ohm657 A (0.66 kA)
0.20 ohm1150 A (1.15 kA)

These values are far below the preferred breaking capacities of 1.5 kA and up, so a device of 1.5 kA or more passes at these points; the check matters most near the origin of a large supply, where the impedance is a fraction of an ohm and the current is much higher.

How this tool works and where the numbers come from

Prospective fault current is Uo divided by the loop impedance; the breaking-capacity requirement is Regulation 434.5.1 of BS 7671.

Sources

Reviewed · Published by WiringCert

Frequently asked questions

Why would I want to know the PSCC?

If the breaking capacity of a protective device is too low for the fault current at its position, the current may destroy the device or cause an electric arc. Knowing the PSCC lets you choose a device whose rating is high enough for that point.

Which breaking capacity values can I choose?

The page offers the preferred miniature circuit-breaker values of 1.5, 3, 4.5, 6, 10, 15, 20 and 25 kA. Choose the value marked on your device, and the page tells you whether the current is within it.

What does BS 7671 require for breaking capacity?

Regulation 434.5.1 of BS 7671 asks for a rated breaking capacity not less than the prospective fault current at the point of installation. The exception is where a back-up device protects that point. This site works to the BS 7671:2018+A4:2026 version.

What is the difference between PSCC and PEFC?

PEFC is the prospective earth fault current, the line-to-earth figure. The line-to-neutral figure is the prospective short circuit current. The page does the same sum for either, so enter the impedance for the one you are checking.

Does the page need an impedance, or can I enter the current?

Either. Enter an impedance and the page divides Uo by it, or enter the kA reading from your tester and the page uses that directly. The link in the address bar keeps your entries.